2 Dell Managed Rack Power Distribution Unit—Product Specifications
Product Specifications
The Dell Managed Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19 outlets.
P
OWER CORD The 3.0 m (10 ft) power cord terminates with an IEC-309, 32 A 3-pin plug (332P6W).
J523N
Electrical
Input connection IEC-309, 32 A 3-pin plug
Acceptable input voltage 220–240 VAC +6%, -10%
Maximum input current (phase) 32 A
Input frequency 50/60 Hz
Input power 7.7 kVA
Output voltage 220–240 VAC (Line-to-Neutral)
Output connections Twenty-one (21) IEC-320-C13 and three (3) IEC-320-C19
Maximum output current (outlet) IEC-320-C19: 16A; IEC-320-C13: 10A
Maximum output current (phase) 32 A
Maximum output current (breaker) 16 A
Overload protection (internal) Two (2) 16 A, 1-pole hydraulic-magnetic circuit breakers
Physical
Dimensions
(H x W x D)
182.9 x 5.6 x 5.5 cm
(72.0 x 2.2 x 2.16 in)
Depth at breakers: 9.4 cm (3.7 in.)
Shipping dimensions
(H x W x D)
207.9 x 22.5 x 15.6 cm
(81.9 x 8.9 x 6.1 in)
Weight 8.9 kg (19.5 lb)
Shipping weight 9.3 kg (20.5 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3 048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
-15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing