Installation
|
Attaching the Ground Wire
To attach the ground wire to the rack:
NOTE:
Dell recommends that you ground the rPDU to the rack frame with the ground wire provided in the Grounding Wire
Kit.
1 Connect one end of the ground wire to the ground bonding point location on the front panel of the rPDU
using the silver, 10-32
0.5 pan-head screw and star washer (supplied).
2 Connect the other end of the ground wire to a hole in the rack frame using the black, M5 12 pan-head
screw and star washer (supplied). See Figure 10.
Ground Bonding Point Connection
10-32
0.5” Pan-head Screw (Silver)
Star Washer
Frame Connection
M5
12 Pan-head Screw (Black)
Star Washer
Figure 10. Ground Bonding Point and Frame Connections
3 Continue to “Connecting Protected Equipment” on page 22.