USER’S GUIDE
Managed Rack PDU
59
olLowLoad
Access: Administrator, Device User, and Outlet User, but only for outlets to which the
user is assigned.
Description: Set or view the outlet low load warning threshold.
Example 1: To set the low load threshold to 2 watts for all outlets, type:
cli> olLowLoad all 2
E000: Success
Example 2: To view the low load threshold for outlets 3 and 5 through 7, type:
cli> olLowLoad 3,5-7
E000: Success
3: BobbysServer: 2 W
5: BillysServer: 2 W
6: JoesServer: 2 W
7: JacksServer: 2 W
Argument Description
all All device outlets.
<outlet
name>
The name configured for a specific outlet. (See olName.)
<outlet#> A single number or a range of numbers separated with a
dash, or a comma-separated list of single outlet numbers
and number ranges.
<power> The new outlet threshold (watts).