Dell Chassis Management Controller Version 4.50 Manual de usuario Pagina 214

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 260
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 213
When Dell OpenManage Power Center management of power is disabled, the CMC reverts to the server priority settings
before the external management was enabled.
NOTE: When Dell OpenManage Power Center management is disabled, CMC does not revert to the earlier setting
of the maximum chassis power. See the CMC log for the earlier setting to manually restore the value.
Configuring Power Budget and Redundancy Using CMC Web Interface
NOTE: To perform power management actions, you must have Chassis Configuration Administrator privilege.
To configure power budget using the Web interface:
1. In the system tree, go to Chassis Overview, and then click PowerConfiguration
The Budget/Redundancy Configuration page is displayed.
2. Select any or all of the following properties as required. For information about each of the fields, see
CMC Online
Help
.
Enable Server Based Power Management
System Input Power Cap
Redundancy Policy
Enable Extended Power Performance
Enable Server Performance Over Power Redundancy
Enable Dynamic Power Supply Engagement
Disable Chassis Power Button
Allow 110 VAC Operation
Enable Max Power Conservation Mode
Enable Remote Power Logging
Remote Power Logging Interval
3. Click Apply to save the changes.
Configuring Power Budget and Redundancy Using RACADM
NOTE: To perform power management actions, you must have Chassis Configuration Administrator privilege.
To enable and set the redundancy policy:
1. Open a serial/Telnet/SSH text console to CMC and log in.
2. Set properties as needed:
To select a redundancy policy, type:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy <value>
where <
value
> is 0 (No Redundancy), 1 (Grid Redundancy), 2 (Power Supply Redundancy). The default is 0.
For example, the following command enables Grid Redundancy mode:
racadm config -g cfgChassisPower -o cfgChassisRedundancyPolicy 1
To enable or disable Extended Power Performance mode, type:
racadm config -g cfgChassisPower -o cfgChassisEPPEnable <value>
where <value> is 0 (disable), 1 (enable). The default is 1 for 3000W PSUs
To set the System Input Power Cap value, type:
racadm config -g cfgChassisPower -o cfgChassisPowerCap <value>