MIB Objects
Table 14. Product Physical Group Variables (continued)
Variable Name and Description
Variable
Unit
Variable
Type
OID
physicalBatteryABMStatus
Advanced Battery Monitoring status:
1: ABM charging
2: ABM discharging
3: ABM floating
4: ABM resting
5: ABM off
UPS.BatterySystem.Charger.Mode
5.1 Integer
physicalBatteryTestStatus
Battery test status:
S Done and Passed
S Done and Warning
S Done and Error
S Aborted
S In progress
S Not implemented
S Scheduled
UPS.BatterySystem.Battery.Test
5.2 Integer
physicalBatterySecondsRemaining
Battery remaining time calculated by the autonometer.
UPS.PowerSummary.RunTimeToEmpty
5.3 Integer Seconds
physicalLoadSegment1ShutdownAfterDelay
Number of seconds remaining until load segment 1 switches off. -1 if no shutdown
countdown is in effect.
UPS.OutletSystem.Outlet[2].DelayBeforeShutdown
6.1 Integer Seconds
physicalLoadSegment1StartupAfterDelay
Number of seconds remaining until load segment 1 switches on. -1 if no startup
countdown is in effect.
UPS.OutletSystem.Outlet[2].DelayBeforeStartup
6.2 Integer Seconds