MIB Objects
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapDCLinkImbalance
DC link imbalance (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced = 1
73 1
trapDCLinkImbalanceOk
DC link imbalance ok
UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced = 0
74 1
trapABMOn (physicalBatteryABMStatus)
ABM state on
Variable: physicalBatteryABMStatusUPS.BatterySystem.Charger.Mode ? 5
79 2
trapABMOff
ABM state off
UPS.BatterySystem.Charger.PresentStatus.Used = 0
80 2
trapLoadSegment1Off
Load segment 1 off
UPS.BatterySystem.Charger.PresentStatus.Used = 0 AND UPS.BatterySystem.Charge.Mode=5
81 2
trapLoadSegment1On
Load segment 1 on
UPS.OutletSystem.Outlet[2].PresentStatus.SwitchOnOff = 1
82 2
trapLoadSegment2Off
Load segment 2 off
UPS.OutletSystem.Outlet[3].PresentStatus.SwitchOnOff = 0
83 2
trapLoadSegment2On
Load segment 2 on
UPS.OutletSystem.Outlet[3].PresentStatus.SwitchOnOff = 1
84 2
trapInHighEfficiencyMode
In High Efficiency mode
UPS.PowerConverter.Input[5].PresentStatus.Used = 1
85 2
trapReturnFromHighEfficiencyMode
Return from High Efficiency mode
UPS.PowerConverter.Input[5].PresentStatus.Used = 0
86 1
trapRectifierOverload
Rectifier input over current
UPS.PowerConverter.Rectifier.PresentStatus.OverLoad = 1
87 2