Vista de pagina 237
cfgSensorRedundancyIndex (Read Only)
Description
Specifies index for the sensor redundancy group being read. Only power supply redundancy is
supported.
Legal Values
1
Default
None
cfgSensorRedundancyPolicy (Read or Write)
Description
Sets the power supply redundancy policy.
Legal Values
2 — N/A, for systems that are not supported
3 — Non Redundant
4–1+1 Redundant
4–2+1 Redundant
16–2+2 Redundant
Default
Any legal value at that particular execution instance.
cfgSensorRedundancyCapabilities (Read Only)
Description
Returns the redundancy capabilities in the form of a bitmask. This bitmask allows the user to know
which values can be set for cfgSensorRedundancyPolicy.
Legal Values
A bit mask. More than 1 bit can be set at a time to indicate multiple redundancy support.
0- N/A, for systems that are not supported
1- Non-Redundant
2- 1+1 — Redundant
4- 2+1 — Redundant
8- 2+2 — Redundant
Default
0
cfgSensorRedundancyStatus (Read Only)
Description
Indicates the redundancy status. The status is N/A on platforms that do not support the power
supply sensor redundancy.
Legal Values
String:
N/A
Full
Lost
Degraded
Default
None